1. Scope
This specification describes the Series CR-1Y Emergency Shut
off System for Chlorine Cylinder and Ton container valves as
manufactured by Halogen Valve Systems, Inc. These systems are
designed for installation in conjunction with automatic switch
over systems (provided by others) employing three chlorine
containers providing an uninterrupted flow of chlorine.
2. Description
The emergency shut off system shall be the Halogen Series CR-1-Y
comprised of three (3) electrically driven Actuators that act
directly upon the cylinder or ton container valve stem. The
Actuators shall mount upon the cylinder or ton container valve
and yoke assemblies by means of a clamping mechanism and a valve
stem coupling so as to be removable during cylinder changes.
The Actuator shall deliver 40-50 Ft.-Lb. of closing torque to the
valve stem upon receipt of a shutdown signal. The Actuator shall
be powered only in the closing direction with provision for manual
override in either the open or closed direction. Power for the
Actuator shall be supplied by an uninterruptable 12V battery power
supply and control system.
3. Actuator Design
Each Actuator shaft shall couple to the valve stem and provide an
extension through the Actuator such that a standard chlorine
wrench may be applied to the extension to manually operate the
valve while the actuator is in place. The extension shaft shall
be coupled to the drive motor and reduction gearing by means of a
one way, positive engagement clutch that may be selectively
disengaged for manual operation. Pushing in on the shaft shall
disengage the clutch for manual operation of the valve. The
clutch shall have a toggle mechanism such that it remains
disengaged, free to rotate in either direction, for manual
operation. The clutch shall automatically reengage, for automatic
closure upon activation of the motor and gear train.
4. Actuator Components
4.1 Motor Driver
Motive power for the Actuators shall be provided by 12V dc
electric motors acting through a gear reduction system.
4.2 Clutch & Shaft
The Actuator shall be constructed of materials suitable for the
chlorine environment. The valve stem extension shaft shall be
machined from a single piece of Monel. The valve stem connection
coupling and shaft bearing/seal shall be of Aluminum-Silicon
Bronze, C-642 Teflon coated for additional corrosion resistance.
The valve stem engagement spring shall be of heat treated Hastelloy
C-276.
4.3 Valve Stem Coupling
The element that couples the driven shaft to the valve stem shall
be designed to accommodate slight misalignment of the Actuator
shaft with the axis of the valve stem without restricting rotation.
4.4 Clamp/Frame
The clamping mechanism for yoke mounting (Series CR-1-Y) shall require no tools for installation on the valve and valve yoke.
Adapters shall be available to unitize the Actuator with regulator clamping systems commonly used in the industry. Regulator mounting shall require only an adjustable wrench for mating to the regulator. The regulator manufacturer is to be specified.
All clamp and frame components shall be coated with fusion bonded polyester for corrosion resistance.
4.5 Sealing Devices
Shaft entrances to the Actuator mechanism shall be sealed with double "O" ring seals of Viton and/or Teflon. The motor canister and main enclosure will be sealed with static, Viton "O" ring seals
5. Control Panel Design
The Triplex control panels shall be contained within a single
electrical enclosure of NEMA 4X rating. All cables, connectors,
switches and fittings shall be of a similar rating to resist the
chemical environment. The actuators shall have a dedicated power
source (battery) and microprocessor controller. Electrical power
shall be delivered to each Actuator by means a flexible cable.
Each individual control panel shall have indicator lights to
display the status of key system elements. The control panel
shall accept signals from sources such as gas detectors, remote
station alarms, seismic or fire sensors and manual switches to
trigger the Actuator or Actuators to automatically close one or
all of the cylinder or ton container valves connected to the
system. The panel shall have the capability of accepting input
signals to initiate either simultaneous or independent operation
of each Actuator and valve.
6. Control Panel Components
6.1 Control circuitry
An electronic circuit board in the control panel shall contain a microprocessor programmed to precisely control the valve closing cycle and the torque applied to the valve stem. The microprocessor shall also monitor and display status of the battery, charging power and system readiness as well as provide a diagnostic system check during the test cycle. Electro-mechanical relays or contacts, which are susceptible to corrosion failure, shall not be used in the control circuitry. The entire control system shall be comprised of encapsulated solid state devices.
In the event of a sustained loss of charging power (seven to ten days), the microprocessor shall detect a declining battery charge to initiate Actuator closure while sufficient power remains to apply the specified torque to the valve stem.
6.2 Battery and Charger
The batteries shall be of the gel-cell lead-acid type rated at 7 ampere-hours. Each charging system shall provide a variable controlled charge current that is temperature compensated to optimize battery performance and service life.
6.3 Status Lights
The control panel enclosure shall have a window in the front cover through which the operator may observe the status lights. The status lights for each respective system are as follows:
1. Charge Power--(Normally On) Green to indicate that charge power is available.
2. Armed/Ready--(Normally On) Rapidly pulsating Green to indicate the microprocessor is functioning and ready to operate. Flashing Green during operation and for a 15 second reset period after activation.
3. Battery Low --(Normally Off) Flashing red to indicate that the battery should be replaced.
6.4 Input Signals
The control panel shall contain a terminal strip to accept multiple incoming signals for either simultaneous or individual Actuator operation. External signals shall consist of a "Normally Open" dry contact, closure to initiate the Actuator.
6.5 Output Signal
Upon initiation of the Actuator, the control system shall provide an output signal (0.2 amp @ 24V dc/ac) to indicate Actuator operation. These may be employed to trigger other displays or alarms.
6.6 Testing
Mounted externally on the control panel shall be a Test switch to provide a full cycle test of the each individual actuator. During the test cycle the microprocessor shall self-test as well as check cable-motor continuity, and the battery under load conditions. Test procedures as outlined on the Actuator and control panel labels shall provide the operator with "Go"-"No-Go" criteria. Test results are confirmed by operator observation and the tactile force required in re-opening the valve.
7. Power Requirements
The power supply to operate the control panel shall be (115 V ac, 60 Hz) single phase. Current consumption shall be 0.5 amp at 115V ac.
8. Options
8.1 Solar Power
Sustaining battery charge power shall be provided by a Siemens M-5 Solar Module rated for 5 Watts at 15V. Solar powered versions shall not require 115 V power.
9. Accessories
Standard accessories for each Actuator system shall include (1) Stowage bracket for temporary placement of the Actuator during cylinder changes. (2) A twisted type chlorine cylinder wrench.